Procurement of Complete set of Oxygen Analyser used In Air Pre-Heater Inlets and Outlets of unit #3,4,5,6, KTPS under CandI dept
The West Bengal Power Development Corporation Ltd. · Mecheda, West Bengal · Electronics & Instrumentation · open
Key facts
- EMD: ₹31K
- Published: 16 Oct 2026
- Closing date: 19 Nov 2026
- Status: open
- Status as of: 12 Nov 2026 04:12 UTC
- Department: C&I Department
- Office: Kolaghat Thermal Power Station (KTPS)
Description
Procurement of oxygen analysers for the air pre-heater inlets and outlets of units 3, 4, 5 and 6 at Kolaghat Thermal Power Station. The BOQ lists one insitu zirconia oxygen analyser set and four zirconia-based oxygen analysers.
Eligibility & requirements
- Startup relaxation: No
- MSE relaxation: No
New to these terms? Read how tender eligibility criteria work.
Commercial terms
- Bid type: Item Rate
- Make in India (MII): No
- MSE preference: No
Line items (2)
- INSITU ZIRCONIA OXYGEN ANALYZER FOR OXYGEN ANALYSER O2 ANALYZER,PROBE WITH CONVERTER SIGNAL OUTPUT 4-20MA DC,DISPLAY RANGE 0 -100%,HART Additional Data: Length:2 meter,Allowable up to 1.8 meter. Materials:ss316, Flange:DIN PN10 /ANSI150-DN50A SUS 304 Probe OD:2''. Probe protector: Material:ss316 Flange:DIN PN10/ ANSI150- DN50A SUS 304 (COUNTER FLANGE SHOULD BE PROVIDED BY VENDOR)OD:3'',ID:2.5'',Length:2050 mm. Out put signal:4-20 ma dc+HART, Power supply:240 v ac,50 hz. Remote Display with Integral Electronics. Connecting wires between analyser to converter need to be provided if required, Cable should be minimum 50 metre in length. Transmitter Option : Standard ZIRCONIA BASED, System Type : Remote Probe Type : Standard , No Automatic Calibration, Probe insertion Length : 2.0 metre, Thermocouple Type : Type k, Standard Cell ;,, Accuracy : 0.05% O2, Response Dead Time : 3 sec., Response rate :T90 is less than 10 seconds, Zero drift & Span drift : < ± 0.2% typically, Output: 4-20mA HART, — Qty: 1 Set
- OXYGEN ANALYSER,ZIRCONIA BASED Additional Data: Length:1 meter,Allowable up to 0.9 meter. Materials:ss316, Flange:DIN PN10/ANSI150- DN50A SUS 304 Probe OD: 2''. Probe protector: Material:ss316 Flange:DIN PN10/ ANSI150- DN50A SUS 304 (COUNTER FLANGE SHOULD BE PROVIDED BY VENDOR) OD:3'',ID:2.5'',Length:1050 mm. Out put signal: 4-20 ma dc +hart, Power supply:240 v ac,50 hz. Remote Display with Integral Electronics.Connecting wares between analyser to converter need to provide if required, Cable should be minimum 50 metre in length.Transmitter Option : Standard ZIRCONIA BASED, System Type : Remote Probe Type : Standard , No Automatic Calibration, Probe insertion Length : 1.0 metre, Thermocouple Type : Type k, Standard Cell ;,, Accuracy : 0.05% O2, Response Dead Time : 3 sec., Response rate :T90 is less than 10 seconds, Zero drift & Span drift : < ± 0.2% typically, Output: 4-20mA+hart. Standart:IP67 — Qty: 4 Number
1 tender document(s) available — sign up to download.
Related tenders
- Television (V3) (4 pieces) — Electronics & Instrumentation · Gujarat · ₹4.0L
- LED (DELL U2725QE) 27INCH WIDE — Electronics & Instrumentation · Jammu and Kashmir
- Interactive Panels With CPU (4 pieces) — Electronics & Instrumentation · Bihar
- HAND HELD SCANNER — Electronics & Instrumentation · Jammu and Kashmir
- PURCHASE OF TTIEG ITEMS — Electronics & Instrumentation · Delhi · ₹1.5L
- Canon Digital Camera With Tripod — Electronics & Instrumentation · Ladakh
- GPS 12H — Electronics & Instrumentation · Assam
- VR GOGGLE PRO 2 — Electronics & Instrumentation · Jammu and Kashmir