LIS Miari – Providing Fitting Commissioning Installation of FASD cum Panel one incomer two outer for two No. three Phase Motors consisting of one 140 Amp. Contactor. Recapitalization of 1 X 75 HP Electric Motor along with reconditioning of 3 Cusec Pump. Earthing of critical Electrical Mechanical Equipment Electrification of Pump House along with connecting works.
Mechanical I and FC Circle Jammu · Miari, Jammu and Kashmir · Repair, Maintenance & AMC Services · open
Key facts
- Tender value: ₹10.0L
- EMD: ₹20K
- Published: 23 Oct 2026
- Closing date: 12 Nov 2026
- Status: open
- Status as of: 04 Nov 2026 05:08 UTC
- Department: I and FC
- Office: Office of the Executive Engineer Mechanical Irrigation Construction Division
Description
Works tender for installation and commissioning of a protection panel and FASD starters, rewinding a 75 HP motor and reconditioning a 3 cusec pump, earthing electromechanical equipment, and electrifying the pump room at LIS Miari.
Eligibility & requirements
- Startup relaxation: No
- MSE relaxation: No
- Certifications: Original Manufacturer’s In-house Test Certificate
- Documents required: Scanned copy of required documents as per requirement of Cover-A, Acceptance of technical specifications and terms and conditions of the tender, duly accepted and signed with seal, Original Manufacturer’s In-house Test Certificate of the Machinery/Equipments at the time of delivery, Bank account number linked with the bidder’s GSTIN
New to these terms? Read how tender eligibility criteria work.
Commercial terms
- Bid type: Item Wise
- Evaluation: Overall lowest aggregate amount of all jobs
- Make in India (MII): No
- MSE preference: No
Line items (5)
- 2 — Qty: 4 5
- Providing/Fitting, Installation, Testing and Commissioning of protection panel cum FASD starters at LIS Miari Description of Panel Designing, fabrication, installation, testing and commissioning of LT control panel 415 volts, AC-3 Phase, 50 Hz. For unit no. 1 and 2, with one incoming and two no outgoing for 75 HP Induction motors at LIS Miari. The panel shall be dust and vermin proof fabricated out of 16 SWG CR Sheet supported on M.S. angle of suitable size and having provision for fixing it on the ground with the help of foundation bolts. The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking/sealing arrangements. The structure should be provided with suitable entry and exit holes for incoming and outgoing cables. The panel should be given two coats of antirust primer and two coats of steel grey enamel paint. The panel should have equipped with following components/features: - M.C.C.B : The panel incomer should be fitted with a main — Qty: 1 Complete Job
- Complete rewinding of the 75 HP electric motor of Pumping unit no. II of LIS Miari by way of dismantling it from the base frame. Shifting by head load to the nearest road side and transportation to workshop done by mechanical means for rewinding. Dismantling of the damaged 75 HP Motor at workshop for extraction of burnt windings, cleaning of stator slots and complete rewinding of the motor with new copper wires of requisite gauge and specification and standard make. Providing/fitting of new insulation, packing material then varnishing with superior quality varnish & drying in oven in controlled temperature. Repair to the rotor shaft of motor done by way of welding, turning and finishing. P/F of bearings 2 Nos. and greasing them properly. Assembling of the stator, rotor and other parts of the motor. Back carriage to site and reinstallation, commissioning and testing on load conditions. Complete job included cost of material, transport charges and labour charges. The job also includes re — Qty: 1 Complete Job
- Complete earthing of the electromechanical equipment’s at LIS Miari Pump Motor sets 2 Nos., LT panel cum starter, voltage stabilizer etc. Job includes excavation of 1 no. pit of size 1.25mx1.25m at the bottom, depth 4 feet at a suitable place near pump house, placing 2 no. copper earthing plate of size 2’x2’ and 4 mm thick in each pit at the bottom of pit, connecting the risers of plates from pit to the ground level. Providing and placing 40mm dia. GI pipe vertically on the copper earthing plates for watering, p/f of plug on the top end of GI pipe. Filling of the pit with four inches thick alternate layers of charcoal and sodium chloride of recommended quality upto height of about 4 feet from bottom of pit and then filling of the pits upto ground level with excavated earth and fitting of copper strips of then connecting all the earthing points of the electrical equipment installed at the site. — Qty: 1 Complete Job
- Electrification of pump room by using standard quality materials as per site requirement for lightening and power circuits by supply and fixing of surface PVC conduit of 20mm size of approximately 30 m length for various light and power points, P/f of 4 no. Led light points/lights inside pump room. The job also includes p/f of 16-amp power socket and 6 ampere charging sockets. P/f of 25 ampere main switch/MCCB for lightening and power circuit. The whole job includes cost of material, hire charges of tools and tackles, charges of skilled and semi-skilled labour at site. — Qty: 1 Complete Job
2 tender document(s) available — sign up to download.
Related tenders
- Rewinding Repairing and testing of 01 no transformer 100 KVA, 11000 415 volt at Jhingurda project — Repair, Maintenance & AMC Services · Madhya Pradesh · ₹1.0L
- Repairing of 02 nos. of clutch plate for 90 HP DATA make direct haulage at no. 2 and B pit under Pandaveswar Colliery, Pandaveswar Area — Repair, Maintenance & AMC Services · West Bengal · ₹3.3L
- Repairing and overhauling of existing outdoor type 800Amp switch of Madhaipur Colliery and Complete Repairing and Renovation of 20/3 Ton EOT Crane at Khottadih UG Workshop under Pandaveswar Area — Repair, Maintenance & AMC Services · West Bengal · ₹15.9L
- (A) Day to day repair and maintenance of LED Street Lights and installation of light control sensor in Street Lights of different places of Kathara Colliery for the period of 02(Two) years i.e. 730 Days or the quantity till exhausted. (B) Comprehensive Annual Maintenance Contract (CAMC) for day to day repairing/maintenance of 440V supply for Staff Colony (Russian Colony, Thakur Colony, Masjid Colony), C-Type Colony and Gayatri Colony for a period of 02(Two) Years. — Repair, Maintenance & AMC Services · Jharkhand · ₹52.5L
- Supply and fitting of electrical items for safe operation at MSAM colliery, Repairing of 01 no of Volcano make 6 stage pump, Job related with workshop nature of repairing and Repairing of 01 no Pluro-II 4 stage pump at South Samla unit of MSAM Colliery — Repair, Maintenance & AMC Services · West Bengal · ₹4.6L
- Overhauling, fabrication,supply, installation,replacement of 1stand2nd Motion pinions alongwith parts of SteamWindingEngine including the supply of necessary materials,fittings required for safe,reliable man-winding operation at 1No Pit Madhaipur UG — Repair, Maintenance & AMC Services · West Bengal · ₹58.1L
- SBSTC/E-TND-01-2nd call for AC Roof top maintenance of 5 VOLVO buses/ DDW/1055 /SBSTC/2026 Dtd. 07 /11/2026 — Repair, Maintenance & AMC Services · West Bengal